Data Centers

The City of Fort Worth aims to protect the health, safety, welfare, and quality of life of residents by effectively leveraging the City’s regulatory authority by requiring best‑in‑class data center development practices.

This page overviews the status of the City’s ongoing work to develop clear standards for data center development in Fort Worth and Frequently Asked Questions (FAQs) about the topic.

Key Dates

June 2, 2026

Proposed regulations and policy amendments presented to City Council.

June 30, 2026

Data Center Regulations Open House

July 8, 2026Zoning Ordinance Amendments were presented to Zoning Commission. The Commission supported stronger regulations, but there was no consensus on amendments. The Commission voted 7-4 for denial.

August 11, 2026City Council moved forward several actions to guide next steps in that process, including: 

  • Initiating the process for a 90-day moratorium on data center development 
  • Establishing the Fort Worth Data Center & Infrastructure Commission (DCIC) 
  • Adopting an application requirement for data centers 

November 3, 2026

Fort Worth Data Center & Infrastructure Commission (DCIC) report to be presented to City Council.

November 10, 2026

First public hearing of the legal process to enact a moratorium on data center development.

 

Fort Worth Data Center & Infrastructure Commission

DCIC Purpose

On August 11, the City Council approved a resolution directing the City to establish an expert commission, the Fort Worth Data Center & Infrastructure Commission (DCIC), to study specific issues and provide a report and recommendations within the City’s regulatory authority to City Council by Nov. 3. 

Led by Mike Slattery, Ph.D., Professor and Director of the Institute for Environmental Studies in the Louise Dilworth Davis College of Science & Engineering at Texas Christian University, the commission of up to 11 members will include individuals representing the economic development business sector, data center operations, environmental/natural resource management, a local electric provider, Tarrant Regional Water District, an environmental advocacy organization and five community members.  

The DCIC’s areas of study include: 

  1. Electricity and Energy 
  2. Water Use and Local Resources 
  3. Land Use, Siting and Neighborhood Impacts 
  4. Economic Development and Fiscal Impacts 

DCIC Members

The Commission’s members, as selected by Dr. Slattery, reflect broad expertise across infrastructure, environment, community perspectives, and industry operations, and will support a rigorous evaluation process:

  • David Berzina, Vice President, JLL
  • Rev. Vernon Elisher, President, Youth & Family Community Outreach Inc.
  • Krista Erbe, Community Organizer, 2871 Community Coalition
  • Dr. Nick Fang, Robert S. Gooch Endowed Professor in Civil Engineering and head of the Water Engineering Research Center (WERC), University of Texas at Arlington
  • Andrew Franko, Principal, Freese and Nichols
  • Rusty Fuller, President, North Fort Worth Alliance
  • Tobi Jackson, Chief Executive Officer, Fort Worth SPARC
  • Ryan Kuithe, Senior Vice President of Facility Operations, QTS Data Centers
  • John MacFarlane, Executive Committee Member – Conservation, Greater Fort Worth Sierra Club
  • Dr. Stathis Michaeledes, W.A. “Tex” Moncrief, Jr. Founding Chair of Engineering at Texas Christian University
  • Ambika Sharma, Community Organizer

The five community representative positions (Elisher, Erbe, Fuller, Jackson, and Sharma) were selected from names put forth for consideration by City Councilmembers.

In addition to the Commission’s voting members, several academic partners have signed on to support DCIC research and synthesis throughout the process. These contributors will help conduct literature reviews, analyze data center impacts, and ensure the Commission’s recommendations are grounded in peer‑reviewed evidence.

  • Dr. Seth Hall (Engineering, Texas Christian University)
  • Dr. Zack Hawley (Economics, Texas Christian University)
  • Dr. Mohammad Islam (Computer Science and Engineering, University of Texas at Arlington)
  • Dr. Gehendra Kharel (Environmental and Geological Sciences, Texas Christian University)
  • Dr. Morgan Kiani (Engineering, Texas Christian University)
  • Dr. Weiwei Liu (Economics, Texas Christian University)
  • Dr. Tom Seng (Assistant Professor of Professional Practice, Texas Christian University)
  • Dr. Bingyang Wei (Computer Science, Texas Christian University)
  • Dr. Fengqi You (Engineering, Cornell University)
  • Dr. Yang Zhou (Economics, University of North Texas)

 

Proposed Regulations for Data Center Development (per June 2 presentation(PDF, 936KB))

Zoning

 Current Zoning Regulations 

No Data Center Specific Standards, follows Industrial Development Standards:

  • Front Setback up to 20 feet if  fronting residential
  • Side Setback of 50 feet adjacent to 1- or 2- family or 5 feet adjacent to other residential
  • Rear Setback of 50 feet adjacent to 1- or 2- family or 10 feet adjacent to other residential
  • Max Height of 3 stories/55 feet in Light Ind. or 12 stories/120 feet in Medium & Heavy Ind.
  • Landscaping and Buffers of 4% net site area or 30-foot depth along roadways
  • Urban Forestry retained and planted canopy coverage of 20% 
  • Within 150 feet of residential district, outdoor lighting must not extend to residential, must be zero foot-candles on residential side, and must not exceed 20 feet in height

 

 Proposed Zoning Amendments

  1. Prohibit Crypto Currency Mining.
  2. Establish Data Center Development Standards:
  • Building setback of 250 feet from residential district and use 
  • Parking and driveways allowed within supplemental building setback 
  • Standby generators not within 300 feet of residential and fully screened
  • Rooftop cooling equipment behind acoustic barrier 1.5 times the height 
  • Extend outdoor lighting regulations to residential use in addition to district 
  • Landscape bufferyard of 50 feet and screening fence along residential
  • A continuous row of evergreen trees at site perimeter adjoining residential 

Noise

 Current Noise Regulations 

Industrial Zoning Districts are exempt from Maximum Sound Levels.

 

 Proposed Noise Amendments

  1. Within 250 feet of residential, require a 72-hour pre-development ambient noise study, measured at property line 
  2. Establish Maximum Sound Levels not to exceed 5 dBA above the pre-development ambient noise 
  3. Require mitigation measures if Maximum Sound Levels are exceeded, at owner/operator expense 
  4. Restrict standby generator testing schedules to weekdays between 8 a.m. and 5 p.m. 
  5. Exempt emergency operations (TCEQ regulated) 

Water

 Existing Water Regulations 

Water Development Review:

  • Water Loading Study required:

    • Identifies water demand for development

    • Tells impact on water system

    • Specifies needed off-site infrastructure improvements

    • Determines meter and tap size

  • Developer pays full cost of extending off-site infrastructure

    • City may contribute for oversizing

  • Water and Wastewater Impact Fees assessed based on meter size

  • Connection Charges assessed

    • Council-adopted Per MGD (Million Gallons Per Day) charge for the water allocation to the specific development

Wastewater Requirements:

  • Required wastewater studies determine impacts, needed improvements, and permit requirements. The permitting process provides:

    • protection of the sewer collection system, 
    • protection of wastewater treatment operations, 
    • protection of utility workers and public health, 
    • prevention of unauthorized chemical discharges, 
    • enforceable accountability measures, 
    • ongoing monitoring and oversight, 
    • and verification/certification requirements that can be investigated and validated by City staff.

 

 Adopted Additional Water Regulations

On August 11, City Council adopted the Installation Policy and Design Criteria for Water, Wastewater, and Reclaimed Water Infrastructure. Updated Policy and Design Criteria requires all new data centers in the Fort Worth Water Utility’s service area to

  • Use closed loop cooling systems

  • Obtain wastewater pretreatment permits as Non-Significant Industrial User (NSIU).

    • NSIU permits may require:

      • chemical disclosure and Safety Data Sheets (SDS) submission, 

      • spill prevention and slug control plans, 

      • secondary containment, 

      • monitoring and inspection access, 

      • discharge limitations, 

      • annual certifications, 

      • employee/operator training, 

      • reporting requirements, 

      • and emergency notification procedures. 

Economic Development

Economic Development Incentives are considered on a case-by-case basis and projects must be fully compliant with adopted City ordinances, policies and plans.

 Current Economic Development Considerations

  • Site appropriateness (zoning, land use, infrastructure capacity, etc.)
  • Site alternatives (competitive sites in other locations)
  • Company track record/financial capacity
  • Project scale (investment minimum)
  • ERCOT approval status and Oncor support
  • Necessity of incentives to address site-specific issue or competitive disadvantage with alternative sites

 

 Proposed Economic Development Policy Changes

  • Demonstrate multiple viable sites under consideration, significant local value in site consideration (i.e. annexation), and clear project improvements tied directly to incentives
  • Demonstrate substantial progress through ERCOT interconnection process before final consideration
  • Significantly exceed policy investment minimum
    • $500 million minimum initial investment and identified end user
    • Requirements for minimum business personal property value throughout life of agreement
    • Limit of grants/abatements to no more than 50% of tax revenue

 

Frequently Asked Questions

What is a Data Center?

A data center is a physical facility that houses IT infrastructure — including servers, storage devices, and networking equipment — used to store, process, and manage digital operations and data.

Any time you send an email, stream a video, use a cloud-based application, access medical records, or make a banking transaction, that request is processed by equipment inside a data center. 

What role does the City have in regulating data center development?

The City of Fort Worth does not control every factor that influences data center development, however, the City does have a role in using local tools to protect the community. 

City of Fort Worth

The City of Fort Worth's authority is focused on four areas: zoning regulations, noise regulations, water utility requirements, and City economic development incentives.  

The City cannot replace state law or regulate areas assigned to state or federal agencies, but it can require local protections when a project comes into the city limits and receives City utility service.

State of Texas

The State of Texas holds authority over several key areas. On energy, the Public Utility Commission of Texas and the Electric Reliability Council of Texas (ERCOT) govern grid access, interconnection, and reliability — meaning the City has no direct control over whether or how a data center connects to the power grid. Statewide water planning falls to the Texas Water Development Board (TWDB). Air quality regulation is the domain of the Texas Commission on Environmental Quality (TCEQ). State tax exemptions and incentives are administered by the Texas Comptroller of Public Accounts and the Texas Economic Development and Tourism Office.

What is a moratorium?

A moratorium is a temporary pause on certain types of new development to allow a city time to study and prepare regulations to address specific development issues. 

Under the Texas Local Government Code, a moratorium requires specific certain requirements, including specific notice and public hearings, written findings to justify the moratorium, and the City must adopt development regulations at the end of the moratorium. Moratoriums have an initial duration of 90 days and may be extended for an additional 90 days provided certain process and findings are followed.   

Moratoriums also have limitations. It cannot be used to regulate issues outside the City’s authority or prohibit a lawful land use. It does not apply to vested projects, approved projects, or those with zoning applications already submitted, meaning projects in progress are not halted.

At the August 11 City Council Meeting, Council adopted a resolution that initiates the legal process to enact a moratorium on new data center development applications while the City completes its regulatory framework.

In accordance with the Council’s direction, the first of the two required public hearings to advance the moratorium process will be held not later than Nov. 10. The City would then need to complete the additional public notices, hearings and ordinance readings as outlined under state law before voting on adoption of the moratorium, tentatively set for Feb. 16, 2027. This action will require a supermajority of the Council to approve and begin the initial 90-day term of the moratorium.  

Should the moratorium be adopted, the City may not impose another moratorium on data center development for two years. 

Are there data centers in Fort Worth?

Yes, there have been data centers operating in Fort Worth for more than two decades. The City currently has four data center developments spanning 10 individual buildings across Council Districts 5 (1 development) and 10 (3 developments), with a combined footprint of more than 3 million square feet. Individual facilities range in size from 209,000 square feet to a 1.5-million-square-foot campus, with an average building size of 275,000 square feet. The first data center in Fort Worth was built in 2000; the most recently completed construction in 2025.

There is also in progress development. Within city limits, one additional facility is currently under construction in Council District 7, and four more have been proposed across Council Districts 3, 6, 7, and 8. Two further data center projects have also been proposed in Fort Worth's extraterritorial jurisdiction. 

Will there be State Legislation about data centers?

It is anticipated that the Texas State Legislature will consider legislation action related to data centers in the next Legislative Session. Several House and Senate Committees are currently studying data center-related interim charges, including impacts on the electric grid, water supply, infrastructure, economic development, and regulation.

During the 89th Texas Legislature (Regular Session), Senate Bill 6 was signed into law and became effective on June 20, 2025. Its purpose was to establish a regulatory framework to manage the rapid growth of consumers with high electricity demand, such as data centers. It sought to address the concerns around grid reliability, cost allocation, data transparency and credibility, and protecting residential customers during grid emergencies.

What is the state of Fort Worth's water supply long-term?

Tarrant Regional Water District (TRWD) is the sole and exclusive provider of raw water to the City of Fort Worth. That contract prioritizes supply for Fort Worth alongside Arlington, Mansfield, and the Trinity River Authority (TRA).

Looking further out, the State Water Plan forecasts that TRWD will need additional water supply over the next 50 years to serve both existing and proposed customers. The plan identifies actionable strategies and financing sources to meet it.

The $2.3 billion Integrated Pipeline project is a cornerstone of the region's long-term supply infrastructure. TRWD is also designing indirect reuse projects at Mary's Creek and Cedar Creek Reservoir, with construction anticipated to begin within the next five years. Additional supply strategies are incorporated into both the State Water Plan and TRWD's own Integrated Water Supply Plan.

The proposed requirement that all new data centers use closed loop cooling systems is consistent with long-range planning strategies.

How much City water do data centers use?

Water use varies by each site's specific operational needs and design.

Estimates normalized to an example of 100 acres of land in Fort Worth:

  • Data center utilizing a closed loop cooling system uses 300,000 - 1 million gallons of water per month on average. 
  • Data center utilizing an evaporative cooling system uses 4 - 6 million gallons of water per month on average.

To put that water use in perspective, a single-family residential development on 100 acres of land in Fort Worth uses approximately 2 million gallons of water per month on average.

How are air emissions and wastewater discharge handled?

Air emissions and wastewater discharge are regulated primarily at the state and federal level through agencies such as Texas Commission on Environmental Quality (TCEQ) and the Environmental Protection Agency (EPA).

Air

TCEQ oversees air quality requirements for data centers in Texas, and reviews air permit applications, regulates emissions standards, and enforces state air quality regulations. The City of Fort Worth responds to air quality complaints. City staff are trained to conduct air quality compliance inspections, to document site conditions, and to refer violations to TCEQ.

TCEQ Permitting

The TCEQ has permits for many different air quality emissions sources.  For data centers, the most common sources of air quality emissions are cooling towers, refrigeration systems, and emergency generators.  It is important to note that a data center’s permit requirements are site-specific based on a facility’s equipment and site design. Permits can vary among: 

• Permit by Rule (cooling towers, refrigerant systems, emergency generators/turbines, fuel storage tanks)

• Standard Permit (power engines & turbines)

• New Source Review (NSR) Permit (sources that don’t meet the criteria for the permitting above)

• Title V Permit (major sources; based on emissions)

Cooling Towers

Cooling towers may be used by data centers to cool down the facility’s equipment.  This is achieved by bringing warm water into contact with cooler air in either a closed loop or open air system. In open air systems, a small amount of water is evaporated to cool the rest of the liquid. 

• TCEQ: Permit by Rule 30 TAC 106.371

Refrigeration Systems

A refrigeration system keeps servers from overheating by removing excess heat using cooling equipment.

• TCEQ: Permit by Rule 30 TAC 106.373

Portable and Emergency Engines & Turbines

Commonly, diesel or gas powered engines and turbines provide backup power, if there is a power outage.

• TCEQ: Permit by Rule 30 TAC 106.511

Stationary Engines & Turbines

Stationary engines and turbines are used as part of a main power system. Unlike portable emergency generators, these systems are built on property to provide regular, ongoing power for the facility.

• TCEQ: Permit by Rule 30 TAC 106.512

Fuel Storage Tanks

Fuel storage tanks hold the fuel necessary to keep engines and turbines running if the main power goes out, or if power is unavailable to the data center.

• TCEQ: Petroleum Storage Tanks (PST): Compliance Resources

For more information about TCEQ air permitting, visit the TCEQ’s Air Permitting webpage at www.tceq.texas.gov/permitting/air/air_permits.html or follow the links below:

TCEQ Cooling Towers & Permits:

TCEQ Cooling Towers Guidance

30 TAC § 106.371—Cooling Water Units

TCEQ Refrigeration Systems & Permits:

TCEQ Refrigeration Systems Guidance

30 TAC § 106.373—Refrigeration Systems

TCEQ Portable and Emergency Generators & Permits:

TCEQ Emergency Generators Guidance

30 TAC § 106.511—Portable and Emergency Engines

TCEQ Stationary Engines and Turbines & Permits:

TCEQ Stationary Engines and Turbines Guidance

30 TAC § 106.512—Stationary Engines and Turbines

TCEQ Fuel Storage Tanks:

PST Compliance Resources

 

Wastewater

The City of Fort Worth’s Water Utility requires wastewater studies to determine impacts, needed improvements, and permit requirements. The permitting process provides:

  • protection of the sewer collection system, 
  • protection of wastewater treatment operations, 
  • protection of utility workers and public health, 
  • prevention of unauthorized chemical discharges, 
  • enforceable accountability measures, 
  • ongoing monitoring and oversight, 
  • and verification/certification requirements that can be investigated and validated by City staff.

Under the 2026 Installation Policy and Design Criteria for Water, Wastewater and Reclaimed Water Infrastructure(PDF, 21MB) , the City requires data centers obtain wastewater pretreatment permits as Non-Significant Industrial User (NSIU). The City issues the NSIU pretreatment permit, in accordance with TCEQ rules and the City’s local ordinance. Doing so allows the City to require and enforce:

  • chemical disclosure and Safety Data Sheets (SDS) submission, 
  • spill prevention and slug control plans, 
  • secondary containment, 
  • monitoring and inspection access, 
  • discharge limitations, 
  • annual certifications, 
  • employee/operator training, 
  • reporting requirements, 
  • and emergency notification procedures. 

What is closed loop cooling?

Closed-loop cooling means the cooling system is designed to reuse water within the system rather than continuously drawing large amounts of new water for cooling operations.

One of the proposed amendments would require that all new data centers use closed-loop cooling systems.

 

 

What does data center electricity use mean for the City?

Data centers do require significant electricity, however, the electric grid is not controlled by the City of Fort Worth. Decisions about grid operations and electric infrastructure are made outside the City’s authority. 

Electric generation, transmission planning, and regional grid reliability are governed through the Electric Reliability Council of Texas (ERCOT), Public Utility Commission of Texas, Oncor, and state law. 

During the 89th Texas Legislature (Regular Session), Senate Bill 6 was signed into law and became effective on June 20, 2025. Its purpose was to establish a regulatory framework to manage the rapid growth of consumers with high electricity demand, such as data centers. It sought to address the concerns around grid reliability, cost allocation, data transparency and credibility, and protecting residential customers during grid emergencies. 

What is the property tax revenue impact of data centers?

Data centers generate an impactful amount of property tax revenue to fund City services and infrastructure. Over the last five years, data centers have generated more than $83 million in gross property tax revenue for the city.

In 2024, gross property tax revenue from data centers equaled the equivalent of what the city collects from roughly 8,300 average single-family homes. By 2030, based on known in progress development, that figure is projected to grow to the equivalent of more than 22,700 homes.